Product Features ■ FRS-1 is flexible structure, suitable for power cable and cable joint wrapping under vary conditions and makes an easy installation ■ FRS-1 prevents fire accidents occurring when it comes to cable joints or cable breakdown; ■ FRS-1 can safeguard cable joints or cables service for longer period in fire accidents; ■ Excellent heat dissipation which will not hinder cables and accessories from heat dissipation under regular service (see temperature rise test).
Download the manualTechnical Parameters
Temperature rise test
NO. | Test item | Requirement | Result | Verdict |
1 | Fire resistance:Dual heat guns, flame up to 750℃, apply AC 8.7kV between conductor and metal shield, apply fire for 90 min | No breakdown on samples during the test | No breakdown | Pass |
2 | Voltage withstand: continue AC 8.7kV for 15min after fire off | No breakdown on samples during the test | No breakdown | Pass |
3 | Sample check: apply 30.5kV for 15min in 1 h after fire off. | No breakdown on samples during the test | No breakdown | Pass |
Time duration | Surface temperature | Conductor temperature |
0 | 20℃ | 20℃ |
10 | 47℃ | 24℃ |
20 | 67℃ | 28℃ |
30 | 87℃ | 33℃ |
40 | 97℃ | 40℃ |
50 | 105℃ | 46℃ |
60 | 111℃ | 50℃ |