35kV Tee Connector

WEB 35/600

Manufactured from EPDM rubber, providing a fully screened separable connection when mated with proper bushing or plug In compliance with IEEE 386, Figure 13 100% factory tested

Download the manual
Voltage Class35kV
Continuous Current600A
AC Withstand Voltage117kV for 5min
Partial Discharge45kV,≤10pC

Impulse Withstand Voltage(10 times for each polarity)

200kV
Screen Resistance≤5000Ω


WEB 35  600.jpg

Design

1. External Screen

Moulded EPDM conductive rubber to ensure the connector touchable

2. Insulation

Moulded EPDM insulating rubber to ensure excellent electrical properties

3. Internal Screen

Moulded EPDM conductive rubber to control electrical stress

4. Two-headed Screw

To secure the conductor lug onto the bushing

5. Conductor Lug

To connect the cable conductor and bushing

6. Insulated Plug

Moulded epoxy plug as described by IEEE 386-2006, Figure 13

7. Cable Adapter

To provide initial stress relief and watertight seal

8. Earthing Wire

To earth the external screen for the connector

9. End Cap

Moulded EPDM conductive rubber to protect against dust

Ordering instruction


1234
WEB



Step 1

Choose the system voltage and current: 35/600

Step 2

Select the range from Table D that fits the diameter over cable insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.

Table D

Diameter over cable insulation

Insulation Range

Code

Diameter over cable insulationφ(mm)
Min.Max.
A
3032
B3235
C3538
D3840
E4042
F4245
G4548
H4851

Table C

Conductor Code

Conductor

 Cross-section

(mm2)

Lug Code

Copper Lug

(Hexagonal 

compression)

Aluminum Lug

(Mechanical Bolted)

5003C

M1

(AULZ25-95-16)

--
7004C

M2

(AULZ70-240-16)

-
9505C-
12006C--
150
07C--
18508C-

​M3

(AULZ185-400-16)

24009C-
30010C--
40011C--
50012C---

Ordering example:

The cable is 35kV, 3*95mm2 copper conductor with core insulation diameter of 34mm. Order WEB 35/600B05C3.

Note: 

Sealing or solderless grounding kits shall be ordered separately. 

Insulated plug with capacitive test point is available upon request.

Please add "-X" for cable with copper wire shield without armour,  like WEB 35/600B05C3-X.