15kV Deadbreak Elbow Connector

WEZT 15/250

Manufactured from EPDM rubber, providing a fully screened separable connection when mated with proper bushing or plug Built-in capacitive test point allows an easy check of the circuit status Equipt with a fault indicator 100% factory tested Tested in compliance with IEC60502.4 In complying with IEEE 386, Figure 4

Download the manual
Voltage Class12kV17.5kV
Continuous Current250A250A
AC Withstand Voltage28.5kV for 5min39kV for 5min
Partial Discharge11kV,≤10pC15kV,≤10pC

Impulse Withstand Voltage(10 times for each polarity)

95kV95kV
Screen Resistance≤5000Ω≤5000Ω


WEZT 15  250.jpg

Design

1. Probe

Tinned copper probe to thread into the conductor lug with the supplied tool

2. External Screen

Moulded conductive EPDM rubber to ensure the connector touchable

3. Insulation

Moulded insulated EPDM rubber to ensure excellent electrical properties

4. Pulling Eye

Provide a detent to position the stainless bail assembly

5. Internal Screen

Moulded conductive EPDM rubber to control electrical stress

6. Voltage Test point

Provide means to check circuit status

7. Earthing Wire

To earth the external screen for the connector

8. Conductor Lug

To connector the cable conductor and probe

Ordering instruction

The ordering formula as followed:


1234
WEZT



Step 1

Choose the system voltage and current: 15/250.

Step 2

Select the range from Table D that fits the diameter over cable insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.

Table D

Diameter over cable insulation

Insulation Range  Code

Diameter over cable insulationφ(mm)
Min.Max.
A
1618
B1721
C2024
D23.527

Table C

Conductor Code

Conductor

 Cross-section(mm2)

Copper Lug

(Hexagonal compression)

Bimetallic Lug

(Hexagonal compression)

2501C01B
3502C02B
5003C03B
7004C04B
9505C05B
12006C06B

Ordering example:

The cable is 15kV, 3*95mm2 copper conductor with core insulation diameter of 20mm. Order WEZT 15/250B05C3.

Note: 

Sealing or solderless grounding kits shall be ordered separately. 

Please add "-X" for cable with copper wire shield without armour,  like WEZT 15/250B05C3-X.

Feel free to contact us for detailed information.