MOA arrester can provide protection for electrical components up to 35kV, such as transformers, equipment, cable and accessories, which may suffer from over voltage and transients resulting from lightning and switching. Designed to comply with the bolted-type Tee connector WEB(K) 35/630 and tested in compliance with IEC 60099.4-2006 and JB/T 8952.
Download the manualItem | WEBK YH5WZ-51/134/400 | WEBK YH5WZ-51/134/600 | WEBK YH5WZ-51/134/800 |
System Nominal Voltage(kV) | 35 | 35 | 35 |
Rated Voltage(kV) | 51 | 51 | 51 |
Continuous Operation Voltage (kV) | 40.8 | 40.8 | 40.8 |
Nominal Discharge Current(kA) | 5 | 5 | 5 |
Steep Current Impulse Residual Voltage (kV) | ≤154 | ≤154 | ≤154 |
Lightning Impulse Residual Voltage(kV) | ≤134 | ≤134 | ≤134 |
Switching Impulse Residual Voltage(kV) | ≤114 | ≤114 | ≤114 |
Long Duration Current Impulse Withstand(A) | 400 | 600 | 800 |
High Current Impulse Withstand (kA) | 100 | 100 | 100 |
Design
1. External Screen
Moulded EPDM conductive rubber ensure the connector touchable
2. Insulation
Moulded EPDM insulating rubber to ensure excellent electrical properties
3. Internal Screen
Moulded EPDM conductive rubber to control electrical stress
4. Two-headed Screw
To secure the conductor lug onto the bushing
5. Copper Connecting Pipe
Connect the lugs between cable and surge arrester
6. Surge Arrester
Metal oxide valve elements.
7. Earth Connection
The surge arrester is connected to the earth by an earth braid
that manages short circuit currents.
8. Earth Lead
Earth the external screen
9. Insulated Plug
Moulded epoxy plug in compliance with the bushing of interface E