36kV Bolted-type Rear Connector

W36CBK

1. External Screen Moulded EPDM conductive rubber to ensure the connector touchable 2. Insulation Moulded EPDM insulating rubber to ensure excellent electrical properties 3. Internal Screen Moulded EPDM conductive rubber to control electrical stress 4. Two-headed Screw To secure the conductor lug onto the bushing 5. Conductor Lug To connect the cable conductor and bushing 6. Insulated Plug Moulded epoxy plug having a metal insert to thread to accept the two-headed screw 7. Cable Adapter To provide initial stress relief and watertight seal 8. Earthing Wire To earth the external screen for the connector 9. End Cap Moulded EPDM conductive rubber to protect against dust

Download the manual
​Voltage Class36kV
Continuous Current630A1250A*
AC Withstand Voltage81kV for 5min
Partial Discharge30kV,≤10pC

Impulse Withstand Voltage(10 times for each polarity)

170kV
Screen Resistance≤5000Ω

Note: * refer to the condition when installed on an appropriate equipment bushing.

W36CBK1.jpg


W36CBK1W36CBK2
L1(mm)197±3200±3
H1(mm)245±5300±5


Design

1. External Screen

Moulded EPDM conductive rubber to ensure the connector touchable

2. Insulation

Moulded EPDM insulating rubber to ensure excellent electrical properties

3. Internal Screen

Moulded EPDM conductive rubber to control electrical stress

4. Two-headed Screw

To secure the conductor lug onto the bushing

5. Conductor Lug

To connect the cable conductor and bushing

6. Insulated Plug

Moulded epoxy plug having a metal insert to thread to accept the two-headed screw

7. Cable Adapter

To provide initial stress relief and watertight seal

8. Earthing Wire

To earth the external screen for the connector

9. End Cap

Moulded EPDM conductive rubber to protect against dust

Ordering instruction

The ordering formula as followed:


1234
W36CBK

Step 1

Choose the highest system voltage: 36kV 

Step 2

Select the connector body size and insulation range code from Table D that fits the diameter over cable insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.

Table D

Connector body size and insulation range code

Connector

Body  Size

Insulation  Range  Code

(For  Cable adaptor)

Applicable Diameter over cable insulationφ(mm)

Min.Max.
1A20
23
B2325
C2528.5
D2831.5
E3135
F3437
G36.539.5
H3942.5
2
I36.540
J39.543
K4347.4
L47.449.5

Table C

Conductor Code

Conductor

Cross-section

(mm2)

Lug Code

Copper Lug Code

(Hexagonal 

compression)

Connector 

Body  

Size*

Aluminum Lug

Code(Mechanical 

Bolted)

Connector 

Body  

Size*

35
02C1

M1

(AULZ25-95-16)

--1
5003C--
7004C

M2

(AULZ70-240-16)

-
9505C-
12006C--
15007C--
18508C--
24009C--
30010C--

M4

(AULZ300-630-16)

2
40011C--
50012C2--
63013C--

Ordering example:

The cable is 36kV, 3*95mm2 aluminum conductor with core insulation diameter of 29mm. Order  W36CBK1DM13.

Note: 

Sealing or solderless grounding kits shall be ordered separately.

Please add "-X" for cable with copper wire shield without armour, like W36CBK1D05C3-X.

Feel free to contact us for detailed information.

*Please make sure the lug code mates with the connector body size if you need to repack the connector kits.