1. External Screen Moulded EPDM conductive rubber to ensure the connector touchable 2. Insulation Moulded EPDM insulating rubber to ensure excellent electrical properties 3. Internal Screen Moulded EPDM conductive rubber to control electrical stress 4. Two-headed Screw To secure the conductor lug onto the bushing 5. Conductor Lug To connect the cable conductor and bushing 6. Insulated Plug Moulded epoxy plug having a metal insert to thread to accept the two-headed screw 7. Cable Adapter To provide initial stress relief and watertight seal 8. Earthing Wire To earth the external screen for the connector 9. Copper Connecting Pipe To connect the cable lugs
Download the manualVoltage Class | 24kV | |
Continuous Current | 630A | 1250A* |
AC Withstand Voltage | 54kV for 5min | |
Partial Discharge | 20kV,≤10pC | |
Impulse Withstand Voltage(10 times for each polarity | 125kV | |
Screen Resistance | ≤5000Ω | |
Screen Fault Current Initiation | For solidly/unearthed /impedance earthed system |
Note: * refer to the condition when installed on an appropriate equipment bushing.
Design
1. External Screen
Moulded EPDM conductive rubber to ensure the connector touchable
2. Insulation
Moulded EPDM insulating rubber to ensure excellent electrical properties
3. Internal Screen
Moulded EPDM conductive rubber to control electrical stress
4. Two-headed Screw
To secure the conductor lug onto the bushing
5. Conductor Lug
To connect the cable conductor and bushing
6. Insulated Plug
Moulded epoxy plug having a metal insert to thread to accept the two-headed screw
7. Cable Adapter
To provide initial stress relief and watertight seal
8. Earthing Wire
To earth the external screen for the connector
9. Copper Connecting Pipe
To connect the cable lugs
Ordering instruction
The ordering formula as followed:
1 | 2 | 3 | 4 | |
WEBK |
Step 1
Choose the system voltage and current: 24/630
Step 2
Select the range from Table D that fits the diameter over cable insulation
Step 3
Select the conductor code from Table C for the conductor size and type
Step 4
Select the package. 1: 1pc/kit; 3: 3pcs/kit.
Table D
Diameter over cable insulation
Insulation Range Code | Diameter over cable insulationφ(mm) | |
Min. | Max. | |
A* | 16 | 19 |
A | 19 | 22 |
B | 22 | 25 |
C | 25 | 28 |
D | 28 | 32 |
E | 32 | 35 |
F | 35 | 38 |
G | 38 | 41 |
H | 41 | 42.5 |
Table C
Conductor Code
Conductor Cross-section (mm2) | Copper Lug (Hexagonal compression) |
25 | 01C |
35 | 02C |
50 | 03C |
70 | 04C |
95 | 05C |
120 | 06C |
150 | 07C |
185 | 08C |
240 | 09C |
300 | 10C |
400 | 11C |
Ordering example:
To fit with WEB24/630, the cable to mate is 24kV, 3-core 95mm2 copper conductor with core insulation diameter of 24mm. Order WEBK 24/630B05C3.
Note:
Sealing or solderless grounding kits shall be ordered separately.
Please add "-X" for cable with copper wire shield without armour, like WEBK 24/630D05C3-X.
Feel free to contact us for detailed information.