24kV Bolted-type Tee Connector

WEB 24/630

1. External Screen Moulded EPDM conductive rubber to ensure the connector touchable 2. Insulation Moulded EPDM insulating rubber to ensure excellent electrical properties 3. Internal Screen Moulded EPDM conductive rubber to control electrical stress 4. Two-headed Screw To secure the conductor lug onto the bushing 5. Conductor Lug To connect the cable conductor and bushing 6. Insulated Plug Moulded epoxy plug having a metal insert to thread to accept the two-headed screw 7. Cable Adapter To provide initial stress relief and watertight seal 8. Earthing Wire To earth the external screen for the connector 9. End Cap Moulded EPDM conductive rubber to protect against dust

Download the manual


Voltage Class24kV
Continuous Current630A1250A*
AC Withstand Voltage54kV for 5min
Partial Discharge20kV,≤10pC

Impulse Withstand Voltage(10 times for each polarity)

125kV
Screen Resistance≤5000Ω
Screen Fault Current Initiation

For solidly/unearthed

/impedance earthed system

Note: * refer to the condition when installed on an appropriate equipment bushing.

WEB 24  630.jpg

Design

1. External Screen

Moulded EPDM conductive rubber to ensure the connector touchable

2. Insulation

Moulded EPDM insulating rubber to ensure excellent electrical properties

3. Internal Screen

Moulded EPDM conductive rubber to control electrical stress

4. Two-headed Screw

To secure the conductor lug onto the bushing

5. Conductor Lug

To connect the cable conductor and bushing

6. Insulated Plug

Moulded epoxy plug having a metal insert to thread to accept the two-headed screw 

7. Cable Adapter

To provide initial stress relief and watertight seal

8. Earthing Wire

To earth the external screen for the connector

9. End Cap

Moulded EPDM conductive rubber to protect against dust

​Ordering instruction

The ordering formula as followed:


1234
WEB



Step 1

Choose the system voltage and current: 24/630

Step 2

Select the range from Table D that fits the diameter over cable insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.

Table D

Diameter over cable insulation

Insulation Range  Code

Diameter over cable insulationφ(mm)
Min.Max.
A*1619
A1922
B2225
C2628
D
2832
E3235
F3538
G3841
H4142.5

Table C

Conductor Code

Conductor  Cross-section

(mm2)

Copper Lug

(Hexagonal compression)

2501C
3502C
5003C
7004C
9505C
12006C
15007C
18508C
24009C
30010C
40011C

Ordering example:

The cable is 24kV, 3-core 95mm2 copper conductor with core insulation diameter of 24mm. Order  WEB 24/630B05C3.

Note: 

Sealing or solderless grounding kits shall be ordered separately. 

Insulated plug with capacitive test point is available upon request.

Please add "-X" for cable with copper wire shield without armour,  like WEB 24/630D05C3-X.