1. Special Lug To connect the cable conductor and apparatus bushing 2. Insulation Moulded insulated EPDM rubber to ensure excellent electrical properties 3. Internal Screen Moulded conductive EPDM rubber to control electrical stress 4. External Screen Moulded conductive EPDM rubber to ensure the connector touchable 5. Earthing Wire To earth the external screen for the connector 6. Voltage test point Provide means to check circuit status
Download the manualVoltage Class | 12kV | 17.5kV | 24kV |
Continuous Current | 250A | 250A | 250A |
AC Withstand Voltage | 28.5kV for 5min | 39kV for 5min | 54kV for 5min |
Partial Discharge | 11kV,≤10pC | 15kV,≤10pC | 20kV,≤10pC |
Impulse Withstand Voltage (10 times for each polarity | 95kV | 95kV | 125kV |
Screen Resistance | ≤5000Ω | ≤5000Ω | ≤5000Ω |
Design
1. Special Lug
To connect the cable conductor and apparatus bushing
2. Insulation
Moulded insulated EPDM rubber to ensure excellent electrical properties
3. Internal Screen
Moulded conductive EPDM rubber to control electrical stress
4. External Screen
Moulded conductive EPDM rubber to ensure the connector touchable
5. Earthing Wire
To earth the external screen for the connector
6. Voltage test point
Provide means to check circuit status
Ordering instruction
1 | 2 | 3 | 4 | |
WEZC |
Step 1
Choose the system voltage and current: 24/250
Step 2
Select the range from Table D that fits the diameter over cable insulation
Step 3
Select the conductor code from Table C for the conductor size and type
Step 4
Select the package. 1: 1pc/kit; 3: 3pcs/kit.
Table D
Diameter over cable insulation
Insulation Range Code | Diameter over cable insulationφ(mm) | |
Min. | Max. | |
A | 16 | 18 |
B | 17 | 21 |
C | 20 | 24 |
D | 23.5 | 27 |
Table C
Conductor Code
Conductor Cross-section (mm2) | Copper Lug (Hexagonal compression) | Bimetallic Lug (Hexagonal compression) |
25 | 01C | 01B |
35 | 02C | 02B |
50 | 03C | 03B |
70 | 04C | 04B |
95 | 05C | 05B |
120 | 06C | 06B |
Ordering example:
The cable is 24kV, 3-core 95mm2 copper conductor with cable insulation diameter of 22mm. Order WEZC 24/250C05C3.
Note:
Sealing or solderless grounding kits shall be ordered separately.
Please add "-X" for cable with copper wire shield without armour, like WEZC 24/250C05C3-X.