Easy, “roll-on” way to insulate and seal cable connections up to 1kV. Made of EPDM rubber, resisting damage from exposure to moisture, ozone, fungus and temperature extremes from -60℃ to 150℃. Dual-wall design with an entrapped lubricant, making installation fast and simple. Rolls on the cable with minimal effort, even at temperature below -25℃. Ideal for use where heating is not allowed. Reusable.
Download the manualEasy, “roll-on” way to insulate and seal cable connections up to 1kV.
Made of EPDM rubber, resisting damage from exposure to moisture, ozone, fungus and temperature extremes from -60℃ to 150℃.
Dual-wall design with an entrapped lubricant, making installation fast and simple.
Rolls on the cable with minimal effort, even at temperature below -25℃.
Ideal for use where heating is not allowed.
Reusable.
Property | Test Method | Standard Value |
Ultimate Tensile | ISO 37 | ≥8.1MPa |
Ultimate Elongation | ISO 34 | ≥750% |
Ultimate Tensile after 136℃x168h | ISO 37 | 9.5MPa |
Ultimate Elongation after 136℃x168h | ISO 34 | 719.89 |
Water Absorption | ISO 62 | 0.3% |
Dielectric Strength | IEC 60243 | 8kV/mm |
Volume Resistivity | ASTM-D-2303 | 1.3x1015 |
Environmental Testing | RoHS | Meet the RoHS |
Salt Spray Test | GB2423 | No crack with ultimate elongation 770 certified by SGS. |
Ozone Test | GB7762 | No crack certified by SGS. |
Low Temperature Ultimate Elongation | -60 ℃x4h | 391.4% |
Product No. | Tube length±5/mm | Application range Cable outer diameter /mm |
WEYB-14 | 160 | 12~20 |
WEYB-25 | 370 | 26~38 |