Manufactured from cross linked polyolefin, inner coated with adhesive at one end. Protecting against accidental flashover. Used in medium voltage cable terminations up to 42 kV. Shrink temperature: start at 90℃, and fully recovered at 130℃. Color: red.
Download the manualProperty | Test Method | Standard Value |
Tensile Strength | ASTM-D-638 | ≥8MPa |
Elongation at Break | ASTM-D-638 | ≥300% |
Tensile Strength Variation After Heat Aging(130℃x168h) | ASTM-D-5510 | ≤±30% |
Elongation at Break Variation After Heat Aging(130℃x168h) | ASTM-D-5510 | ≤±30% |
Volume Resistivity | IEC 60093 | ≥1x1014Ω.cm |
Dielectric Strength | IEC 60243 | ≥20kV/mm |
Tracking Resistance | IEC 60587 | 1A 3.5 |
Dielectric Constant | IEC 60250 | ≤5 |
Heat Shock | 160℃,4h | No Crack |
Water Absorption (23±2)℃ 24h | ISO 62 | ≤0.1% |
Hardness(Shore A) | ISO 868 | ≥80 |
Brittle Temperature | ISO 974 | -40℃ |
Spec. | As Supplied/mm | After Recovered/mm | Standard Cut Length /mm | Standard Continuous Length (m/roll) | ||
Inner Diameter Min | Wall Thickness (±0.3) | Inner Diameter Max | Wall Thickness (±0.3) | |||
WRSJG-30/12 | 30 | 1.0 | 12 | 2.2 | 600-1200 | 25 |
WRSJG-35/14 | 35 | 1.0 | 14 | 2.3 | 600-1200 | 25 |
WRSJG-40/17 | 40 | 1.0 | 17 | 2.3 | 600-1200 | 25 |
WRSJG-50/22 | 50 | 1.0 | 22 | 2.5 | 600-1200 | 25 |
WRSJG-35/13 | 35 | 1.2 | 13 | 3.0 | 600-1200 | 25 |
WRSJG-40/15 | 40 | 1.2 | 15 | 3.0 | 600-1200 | 25 |
WRSJG-50/19 | 50 | 1.1 | 19 | 3.0 | 600-1200 | 25 |
WRSJG-55/24 | 55 | 1.4 | 24 | 3.2 | 600-1200 | 15 |
WRSJG-60/26 | 60 | 1.4 | 26 | 3.2 | 600-1200 | 15 |
WRSJG-70/29 | 70 | 1.4 | 29 | 3.2 | 600-1200 | 15 |
WRSJG-75/35 | 75 | 1.5 | 35 | 3.2 | 600-1200 | 15 |
WRSJG-80/36 | 80 | 1.4 | 36 | 3.2 | 600-1200 | 15 |
WRSJG-90/41 | 90 | 1.6 | 41 | 3.5 | 600-1200 | 15 |
WRSJG-100/45 | 100 | 1.5 | 45 | 3.5 | 600-1200 | 15 |