WOER(002130):0.000.00(0.00%)

250A Plug-in Type Elbow Connector WEZT 24/250

WEZT 24/250

Download the manual

Design

  • Probe Tinned copper probe to thread into the conductor lug with the supplied tool
  • External Screen: Moulded conductive EPDM rubber to ensure the connector touchable

  • Insulation: Moulded insulated EPDM rubber to ensure high quality
  • Pulling eye: Provide a detent to position the stainless bail assembly
  • Internal Screen: Moulded conductive EPDM rubber to control electrical stress
  • Voltage test point: Provide means to check circuit status
  • Earthling Wire: To earth the external screen for the connector
  • Conductor Lug: To connector the cable conductor and probe

Technical Data

Voltage Class 12kV17.5kV24kV
Continuous Current250A250A250A
AC Withstand Voltage28.5kV for 5min39kV for 5min250A
Partial Discharge11kV, ≤10pC15kV, ≤10pC54kV for 5min
Impulse Withstand Voltage (10 times for each polarity)95kV95kV20kV,≤ 10pC
Overload Current(8 hrs Max)300A300A300A
Screen Resistance≤ 5000Ω≤ 5000 Ω≤ 5000 Ω

Ordering instruction

The ordering formula as followed:       1    2     3    4
WEZT    
  

Step 1

Choose the system voltage and current: 24/250

Step 2

Select the range from Table D that fits the diameter over core insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.


Ordering example:

The cable is 24kV, 3-core 95mm2 copper conductor with core insulation diameter of 22mm. Order WEZT 24/250C05C3.


Note:

Solderless grounding kits shall be ordered separately.

Feel free to contact us for detailed information.

Table D

Diameter over core insulation

Insulation Range CodeDiameter over core insulation φ(mm)
Min.Max.
A1618
B1721
C2024
D23.527

Table C

Conductor Code
Conductor Cross-section(mm2)Copper Conductor (Hexagonal compression)Aluminium Conductor (Hexagonal compression)
2501C01B
3502C02B
5003C03B
7004C04B
9505C05B
12006C06B
Back