WOER(002130):0.000.00(0.00%)

250A Plug-in Type Straight Connector WEZC 24/250

​ Design

  • Special Lug: To connector the cable conductor and apparatus bushing
  • Insulation: Moulded insulated EPDM rubber to ensure high quality
  • Internal Screen: Moulded conductive EPDM rubber to control electrical
  • External Screen: Moulded conductive EPDM rubber to ensure the connector touchable
  • Earthing Wire: To earth the external screen for the connector
  • Voltage test point: Provide means to check circuit status

Technical Data

Voltage Class   12kV 17.5kV 24kV
Continuous Current 250A 250A 250A
AC Withstand Voltage 28.5kV for 5min 39kV for 5min 250A
Partial Discharge 11kV, ≤10pC 15kV, ≤10pC         54kV for 5min
Impulse Withstand Voltage (10 times for each polarity) 95kV 95kV 20kV,≤ 10pC
Overload Current(8 hrs Max) 300A 300A 300A
Screen Resistance ≤ 5000Ω ≤ 5000 Ω ≤ 5000  Ω

Ordering instruction

The ordering formula as followed:
  1    2     3    4
WEZC    
  

Step 1

Choose the system voltage and current: 24/250

Step 2

Select the range from Table D that fits the diameter over core insulation

Step 3

Select the conductor code from Table C for the conductor size and type

Step 4

Select the package. 1: 1pc/kit; 3: 3pcs/kit.


Ordering example:

The cable is 24kV, 3-core 95mm2 copper conductor with core insulation diameter of 22mm. Order WEZC 24/250C05C3.

Note:

Solderless grounding kits shall be ordered separately. Feel free to contact us for detailed information.

Table D

Diameter over core insulation

Insulation Range CodeDiameter over core insulationφ(mm)
Min.Max.
A1618
B1721
C2024
D23.527

Table C

Conductor Code
Conductor Cross-section(mm2)Copper Conductor (Hexagonal compression)Aluminium Conductor (Hexagonal compression)
2501C01B
3502C02B
5003C03B
7004C04B
9505C05B
12006C06B
Back