WOER(002130):0.000.00(0.00%)

RSFRNH-BTM

Medium Voltage Cross-linked Polyolefin Bus-Bar Tubing

Medium Voltage Cross-linked Polyolefin Bus-Bar Tubing

RSFRNH-BTM is made from specially formulated radiation cross-linked halogen free compounds. It can provide high resistance to tracking and arcing, as well as to enhance the insulation properties of bus-bar in switchgear and substation. Suitable for application in insulating medium voltage bus bars, cable termination and joints from 1KV to 24KV.

Features

  • Flame Retardant
  • Reduces bus bar clearance requirements
  • Protect against accidental flashover
  • Anti-track
  • Halogen free
  • Tested to IEC60684 standards for medium voltage
  • switch-gear applications to above 20KV
  • Continuous Operating Temperature:  -40 ℃ to 110℃ ,can be used in 175℃
  • Shrink Temperature:120℃

    ​Technical Data

    Physical

    PropertyTest MethodStandard PerformanceTypical Performance
    Tensile strengthIEC 60684≥8Mpa10.5 Mpa
    ElongationIEC 60684≥400%550%
    Heat Aging tensile strength150℃╳168h≥5Mpa9.5 Mpa
    Heat Aging elongation150℃╳68h≥200%450%
    Heat shock225℃╳4hno cracking or flowingno cracking or flowing
    FlammabilityIEC 60684PassedPassed
    Low temperature Flexibility-40℃*4hno crackingno cracking

    Electrical

    PropertyTest MethodStandard PerformanceTypical Performance
    Dielectric StrengthIEC 60684≥20KV/mm23kv/mm
    Volume ResistivityIEC 60684≥1×1013Ω•㎝2×1014Ω•㎝
    Tracking(2.5kv,60min)IEC 60684no crackingno cracking


​Selection Table

Normal size   (mm)As Supplied/mmAfter Recovered/mmStandard Package   (m/roll)
Inside diameterInside diameter(Max)Wall Thickness(Min)
Φ20/62062.2±0.325
Φ28/92892.6±0.325
Φ33/1033102.8±0.325
Φ40/1240122.8±0.325
Φ45/1445143.0±0.325
Φ55/1655163.0±0.325
Φ65/1965193.0±0.325
Φ75/2275223.0±0.325
Φ85/2585253.2±0.325
Φ95/3095303.2±0.325
Φ115/34115343.3±0.325
Φ130/36130363.3±0.325
Φ160/50160503.3±0.325
Φ180/56180563.3±0.325


Back