Type/Applications: Cross Bonding Link Box: WJC
Product Introduction
Cross bonding link box is used for cross interconnection of high-voltage single-core cable metal sheath, limiting over voltage applied to cable sheath and both insulated part ends of insulated joint, controlling induced voltage on metal sheath, reducing or eliminating ring current on cable sheath, increasing transmission capacity of power cable, avoiding oversheath breakdown, to ensure a safe operating for per cable. With stainless steel enclosure, link box could be filled by resin inside, at the main time, link box is volume-small, weight-light, installation-easy and limiter removable.
Main Electrical Property of Link boxes
No. | Test Item | Technical Requirements |
1 | DC voltage withstand test | Nether breakdown nor flashover shall occur at 20kV for 1 min |
2 | Impulse voltage test | Nether breakdown nor flashover shall occur at 10 positive and 10 negative impulse of 40kV (peak value) |
3 | Insulation resistance test between copper bar and housing | Not less than 20MΩ |
4 | Contact resistance test of copper bar | Not less than 20μΩ |
Main Electrical Property of SVL
No. | Test Item | BHQ-7/600 | BHQ-10/600 |
1 | DC 1mA reference voltage | 4kV | 5.8kV |
2 | Rectangular wave capacity | 600A | 600A |
3 | Residual voltage ratio | K≤2 | K≤2 |
4 | Current capacity | 100kA | 100kA |
5 | Rated voltage | 2.8kV | 4kV |
6 | Residual voltage of nominal discharge current | ≤7kV | ≤10kV |