WYJZGG: Indoor only
Type/Applications:
WYJZGG: Indoor only
Rated voltage:48/66kV,applicable to 120 ~1600mm2
Rated voltage:64/110kV,applicable to 240 ~1600mm2
Rated voltage:76/138kV,applicable to 240 ~1600mm2
Rated voltage:127/220kV,applicable to 400 ~2500mm2
Features:
1. Stress cone is injection-molded by imported EPDM rubber. Secured by the spring cone carrier, our stress cone is designed with a stress cone cover so as to be isolated from insulated agent (avoiding poor contact between stress cone and cable outer semi-conductive layer or elastic relaxation due to stress cone ageing) ensures excellent electrical property.
2. Dry design eliminates risks of oil or gas leakage
3. Compact design with lightweight and small volume significantly saves mounting space.
4. Plug-in connection between termination and cables provides more convenient installation and maintenance.
5. Plug-in type GIS termination is suitable for connection between power cable and transformer.
6. Short type plug-in GIS termination can be refitted to equipments applicable to a long type GIS termination kit after assembled with an extending rod.
Outline Dimension
Voltage Rating | A(mm) | B(mm) | C(mm) | D(mm) | E(mm) | H(mm) | Q(mm) | R(mm) |
66 kV | 300 | 270 | 245 | 185 | 10 | 310/583 | 80 | 110 |
110 kV | 350 | 320 | 298 | 210 | 12 | 470/757 | 80 | 110 |
138 kV | 350 | 320 | 298 | 210 | 12 | 470/757 | 80 | 110 |
220 kV | 620 | 582 | 559 | 340 | 12 | 620/960 | 100 | 200 |