600A Deadbreak Reducing Tap Plug with Bushing Extender

600A Deadbreak Reducing Tap Plug with Bushing Extender

Description:                                                                                                                       Detailed Specification Download   

  • 600A Deadbreak Reducing Tap Plug with Bushing Extender
  • Providing a fully shielded, submersible, threaded connection for mated deadbreak operation
  • Using with deadbreak components meeting the requirements of IEEE 386
  • Compact design
  • Transition of a 600A deadbreak system to a 200A loadbreak system, with the 600A interface connecting to bushing or junction and 200A loadbreak bushing interface
Technical Data
Rated Voltage 8.3/14.4kV
Rated Current 600A
AC Withstand Voltage 34kV for 1min
Partial Discharge 11kV,≤3pC
Impulse Withstand Voltage (10 times for each polarity)
95kV
Screen Resistance ≤5000Ω

 

600A Deadbreak Insulated Cap

  • Made of EPDM rubber
  • Used to insulate, shield and seal the deadbreak interfaces of 600A bushings per IEEE 386
  • Compact design
  • Tested in compliance with IEC 60502.4-2005
  • 100% factory tested

Technical Data

Rated Voltage 8.3/14.4kV
Rated Current 600A
AC Withstand Voltage 34kV for 1min
Partial Discharge 11kV,≤3pC
Impulse Withstand Voltage (10 times for each polarity)
95kV
Screen Resistance ≤5000Ω