200A Loadbreak Insulated Cap

200A Loadbreak Insulated Cap

Description:                                                                                                                       Detailed Specification Download   

  • Made of high quality EPDM rubber
  • Used to insulate, shield and seal the loadbreak interface of 200A bushings
  • In compliance with IEEE 386
  • 100% factory tested  

Technical Data

Item WAJM 15/200
Rated Voltage (U0/U) 8.3/14.4kV
Rated Current 200A
AC Withstand Voltage 34kV for 1min
Partial Discharge 11kV,≤ 3pC
Impulse Withstand Voltage (10 times for each polarity) 95kV
Screen Resistance ≤5000Ω

 

200A Loadbreak Elbow Connector with Surge Arrester

  • Fully screened and insulated
  • Protecting electrical components against over-voltage and transients
  • The surge arrester’s active part is made of metal oxide
  • The connected braid to manage short circuit currents
  • In compliance with IEC 60099.4-2006, JB/T 8952
  • 100% factory tested
  • Made of high quality EPDM
 

 

Technical Data

Item WAZT-BLQ-17/45 WAZT-BLQ-17/50
SystemNominalVoltage(kV) 15 15
RatedVoltage 17 17
ContinuousOperationVoltage (kV) 13.6 13.6
DC(1mA) ReferenceVoltage(kV) ≥24 ≥25
SteepCurrentImpulseResidualVoltage (kV) ≤51.8 ≤57.5
LightningImpulseResidualVoltage(kV) ≤ 45 ≤ 50
SwitchingImpulseResidualVoltage(kV) ≤35 ≤42.5
LongDurationCurrentImpulseWithstand(A) 150 100
HighCurrentImpulseWithstand (kA) 65 65